Temperature Sensor Module
Overview
AirCare’s ACM1016H Temperature Sensor Module
provides a 0-5 volt output relative to a temperature at
the sensor surface. The ACM1016H, along with the
AirCare VariPhase™ (ACV1xxx) can provide either
closed-loop, regulated temperature for fan-controlled
systems or open loop primary set point control. Once
configured, the system will automatically adjust fan
speed to in response to changing temperatures.
The ACM1016H may be used only in air or
nonconductive gas environments; Liquids or
corrosive gases will damage the unit.
Product Description
The ACM1016H uses a thermistor bridge control
circuit to provide a 0-5 volt analog signal to the
controller based upon the measured temperature. The
unit adjusts the dc output voltage around the mid-point
setting of the sensor. The ACM1016H provides small
size, ruggedness and excellent stability with reduced
drift. The ACM1016H can be powered from the 12V
output of AirCare VariPhase or from any 12Vdc
source.
The ACM1016H range can be customized from 0°C to
50°C with the pre-mounted thermistor on the PCB.
Higher temperatures can be accommodated using an
off-board thermistor. The ACM1016H provides linear
control over +/- 50% of the mid-point temperature,
which is designed to provide 2.5 volts output. A 1
degree change in temperature equates to 50mV change
to the output of the ACM1016H. Custom ranges can
also be accommodated.
Specification
Local power supply : 9.5-15Vdc
Simple connections:
Screw Terminals for output
Open-frame PCB with mounting bracket or
optional rugged enclosure
Operating Temperature:
o PCB Mounted:
0-50°C
o External Thermistor
Higher temp. available
5.5” x .5” x .06” (board only)
Current Draw: 50mA (max)
Mid-Point and Range customized.
Typical 1% change in temperature = <2%
change in full range dc voltage (output)
Installation
The ACM1016H is provided with a
mounting bracket to allow easy placement.
A three wire cable is provided that will
connect to the terminal strip and the
controller. The unit can also be provided in a
protected casing for greater board
protection. Place the ACM1016H in a stable
environment for best results.
The ACM1016H dc output can be used to
either set the controller speed (analog
control) or be used for closed loop control
(feedback control signal) of temperature
using an external setting. The ACM1016H
is not linear over the full range (0-100%); It
is quite linear over mid-point range. The
curve below shows the setting output (on a
0-100% scale) vs. Temperature.
Probe Temp. Vs Console Setting
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
100.0
110.0
30 40 50 60 70 80 90
Console setting
Temp C
Figure 1 Analog output from Sensor as % of
full voltage for temperatures shown.
ACM1016H
Email: info@aircareautomation.com Website: www.aircareautomation.com
8204 N. Lamar, Suite B-11 Austin, TX 78753. Tel: (512) 249-7526 Fax: (512) 275-6155
Rev1.1 10/16/08
|
|