ACS2302 Relay Module
Overview
The ACS2302 is a packaged dry contact relay to mount
adjacent to the ACM1009 relay for dry-contact
communication to a Building Management System.
Assembly is made through terminal strip contacts easing field
installation
Specifications
- Package 1.58 x 1.58 x .59 (inches)
- Mounting flange centers 1 7/8
- Connector 5.08mm centers, Screw terminals
- Recommended wire gauge = 20
Relay Information
- Relay Voltage - Nominal 12Vdc ( 9 min, 25 max.)
- Relay Resistance 1 KOhms ( 12mA nominal)
- Relay Contact = Form C, SPD single pole 2 position.
- Relay Max. Contact current 2A.
Product Description
The ACS2302 is small plastic package with a dry contact
relay and terminal strip pre-wired to mate with the
ACM1009 and provide isolated contact opening or closure to
a building management system when the High or Low Limit
Alarm is activated.
Installation
The ACS2302 can be mounted in any orientation. Distance
from the ACM1009 is limited only by wire size and
voltage drop.
Mount the ACS2302 securely with two (2) #6
screws through the flanges. The relay should be
mounted in a location that protects it from moisture
and environmental extremes
.
ACS2302_____
Email: info@aircareautomation.com Website: www.aircareautomation.com
8204 ). Lamar, Suite B-11 Austin, TX 78753. Tel: (512) 249-7526 Fax: (512) 275-6155
Coil NC Pole NO
1.58”
1.875”
Rev 1.2
|
|