Parameter Min Typical Max
Input Voltage Range 115V unit 95V 115V 135V
Input Voltage Range 230V unit 200V 230V 260V
Input Voltage Range 277V unit 250V 277V 305V
Supply Frequency (Hz) 50/60 Hz
Output Current (Arms) Continuous See table
Output Current (Arms) 30 seconds 125%
Output Voltage (Vac) 0 Vin
Ambient Operating Temperature (ºC) 0 25ºC 40ºC
Standby Supply Power <2W
Insertion Loss (V) 1V 2V
Control Power Loss (W) 1W/Amp 2W/Amp
Isolation Voltage (Vrms) 2500V
Sensor Supply Voltage Output (Vdc) 5V/12V
Sensor Supply Current Output (mA) 25mA
AirCare VariPhase ™
Overview
The AirCare VariPhase™ is a Network or Analog controlled
Fan/Blower Control for use with Single-Phase Permanent Split
capacitor (PSC) or Shaded-Pole Induction Motors. Capable of 8
ampere in 115, 230, and 277 volt models, these controls offer a 3-
wire (higher efficiency and lower noise) or traditional 2-wire
connection option. Open-loop or Closed-loop operation is
selectable. AirCare VariPhase™ has network connectivity
(MODBUS® RTU-based) through RJ45 to any controller or
AirCares’ Proprietary Control System. Analog Control input
allows manual control or analog inputs from any PLC or system
controller.
PRODUCT DESCRIPTIO
AirCare VariPhase™ controls combine intelligent speed control
with industry standard MODBUS® RTU networking. The
versatile design allows for either analog (0-5V or 20mA) or
network speed control. In network mode VariPhase™ units can
have up to 125 unique addresses that can be precisely controlled
from our proprietary AirCare Console™., AirCare system
controller your PLC or Building Management System (BMS).
For optimal efficiency and reduced acoustic noise, VariPhase™
models include intelligent auxiliary winding control using a 3rd
wire to the motor. Soft-start options are also available. Permanent
Split Capacitor (PSC) motor loads can be connected in three-wire
mode or wired conventionally for standard operation.
RPM speed regulation control utilizes an external hall-effect
sensor (counter through “HALL” connection) to precisely control
and monitor fan speed. An internal PID controller provides
system loop stability customized for your system.
“Closed Loop Control” mode uses the second Analog Input
(ANA2) that allows for closed loop control of the speed to any
controlled parameter that can provide a 0-5 volt feedback signal.
The PID parameters can be adjusted to provide stable controlled
operation.
Installing a distributed network of AirCare controls is simplified
by flexible wiring options and diagnostic LEDs.
Electrical Parameters
Model Matrix
Communications
• MODBUS® RTU Protocol
• Selectable wiring - RS422 (4 wire), or RS485(2 wire)
• Selectable baud rate- 1200 or 9600, 8 n, l
• Dual RJ45 sockets (2 and 4 wire) for communication
• Field selectable addressing
• Supports up to 127 devices per Network
• Slew rate control for improved performance
Features
• 3-wire or 2-wire control
• Automatic 50Hz or 60Hz
• Soft-Start (adjustable) enabled
• “Speed set memory” resets to last setting under power loss
• Open Loop Analog Control input (0-5Vdc, 0, 4-20mA)
• Closed Loop Control to external Sensor (i.e. pressure,
temperature) to regulate fan speed to external (0-5 volt
feedback) criteria
• Speed Regulation option (external hall sensor feedback)
-Measures and controls actual speed
• Open-frame (UL approved, NEMA 1 cover optional)
• Diagnostic LED’s:
-Status/Fault
-Network Traffic
• Overload: 150% for 30 seconds
• Analog PID controller for closed-loop sensor
operation
.
Model Voltage
Rating(AC)
Current
Rating
ACV 1081U 115V 8.0A
ACV 1082U 230V 8.0A
ACV 1083U 277V 8.0A
Rev. 1.2 11/08
ACV1081U
ACV1082U
ACV1083U
Email: info@aircareautomation.com Website: www.aircareautomation.com
8204 . Lamar, Suite B-11 Austin, TX 78753. Tel: (512)249-7526 Fax: (512)275-6155
V-SERIES
CE approved and ETL certified to UL508C.. Contact factory for more details.
|
|