Air-Flow Sensor
Overview
AirCare’s ACM1006A Air-Flow Sensor Module
provides a 0-5 volt output relative to an air-flow over
the sensor surface. The ACM1006A, along with the
AirCare VariPhase™ (ACV1xxx) can provide closedloop,
regulated airflow for fan-controlled systems. Once
set-up and configured, the system will automatically
adjust fan speed to maintain airflow at the desired set
point. The ACM1006 maybe used only in air or with
nonconductive gases. Use with liquids or corrosive
gases will damage the unit.
Product Description
The ACM1006A uses a thermistor bridge to provide
feedback to the controller based upon air-flow over the
surface of the sensor. The unit has built-in temperature
compensation and offers linear air-flow feedback
around the mid-point setting of the sensor. The
ACM1006A provides small size, ruggedness, excellent
stability and reduced drift versus hot-wire solutions.
The ACM1006 can be powered from the 12V output
of AirCare’s VariPhase or an external 12Vdc source.
The ACM1006A can be customized from 75FPM to
500FPM for your output needs. The ACM1006A
provides several set-point ranges to cover most airflow
applications. At the set-point (2.5 volts) the
ACM1006A provides linear control over +/- 50% of
the set-point. A 1-2% change in airflow equates to
50mV change to the output of the ACM1006A.
Specification
Local power supply : 9.5-15Vdc
Simple connections:
Screw Terminals for output
Open-frame PCB with mounting bracket or
optional rugged enclosure
0-50°C operating temperature
5.5” x .5” x .06” (board only)
Current Draw: 50mA (max)
Set Point and range customized.
Typical 1% change in Set point = 1-2%
change in set-point air-flow .
Installation
The ACM1006A can be mounted in various
locations to maintain airflow. Whether in
the laminar flow of an FFU, or the venturi
inlet of a fan filter unit, or in turbulent the
air-flow stream, the ACM1006A enables
continuous air-flow monitoring and
adjustments. Application Note 1010
provides additional information.
ACM1006A is designed to provide closed
loop control of air flow at a set point. It
provides linear voltage feedback for small
changes (less than 50%) in the set point, but
is not linear over the full range of Set Point
(0-100%). The curve below shows the
voltage feedback vs. the airflow.
ACM1006A
Email: info@aircareautomation.com Website: www.aircareautomation.com
8204 /. Lamar, Suite B-11 Austin, TX 78753. Tel: (512) 249-7526 Fax: (512) 275-6155
Rev1.5 5/16/2007
ACM1006A Output Voltage vs Air flow
(Centered at 100FPM)
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
40 60 80 100 120 140 160 180 200
Flow FPM
Output Voltage
|
|