| | MODEL | 3100 3120 3160 | 3200 3250 3300 | |
| | 1 Power(kVA) | 100 120 160 200 250 300 | |
| | INPUT | | |
| | Input Voltage | 220/380 Vac 3 Phase + Neutral +/- %15 | |
| | By-Pass Voltage | 220/380 Vac 3 Phase + Neutral +/- %10 | |
| | Input Frequency | 50 Hz (Optional 60 Hz) +/- %5 | |
| | EMC | EN50091-2 Class A | |
| | OUTPUT | | |
| | Power(kW) | 80 96 128 160 200 240 | |
| | Power Factor | 0,8 | |
| | Voltage | 220/380 Vac 3 Phase + Neutral | |
| | Voltage Tolerance | (Balanced Load +/- %1) (Unbalanced Load +/- %2) (Sudden Loading +/- %5) | |
| | Voltage Balance Time | Max. 25 msn. After Sudden Loading | |
| | Frequency | 50 Hz (Optional 60 Hz) | |
| | Frequency Tolerance | (Synchronised to line: +/-%2) (Free Operation: +/-%0,2) | |
| | Efficiency (at % lOOLoad) | % 89-91 % 90-92 | |
| | Crest Factor | 3:1 | |
| | Over Load | (at % 100-%125 load: 10 dk.) (at % 125-%150 Load: 1 dk.) (>% 150 Load: By-Pass) | |
| | Shortcircuit Protection | Available | |
| | THD | At Linear Load: < %3 | |
| | THD | At Non Linear Load: < %5 | |
| | BATTERY | | |
| | Type | Dry Type Maintanence Free | |
| | Battery No | 30 | |
| | Charge Voltage | 405VDC | |
| | End of Discharge Volta | |e 300VDC | |
| | Battery Protection | Automatic Circuit Breaker | |
| | Battery Test | Automatic Per 72 hours | |
| | DISPLAY | | |
| | Type | 5 Button and LCD | |
| | LCD Display | Input-Output Voltages, Frequency ,Load ,Battery Voltage and Charge Current, UPS inner heat and various alarms monitoring ON LCD Screen. Date and Hour Display: 64 recorded Alarm Memory | |
| | LED Display | LEDs for(Load at By-Pass, Load at UPS and Operation From Batteries) | |
| | GENERA | L | | |
| | Serial Communication | DryContactand RS232 | |
| | Software | T-MonUPS ManaqementSoftwcre | |
| | Operation Temperature | 0C-40C | |
| | Cooling | Forced Cooling | |
| | Humidity (Not Condensed) | < 90 % | |
| | Protection Class | ^^^^^^^^^^^^^^^m IP20 | |
| | Operation Height | < 1000 m. From Sea Level | |
| | Noice Level | <65dBA | < 70 dBA | |
| | Weight (Without Battery) | 770 810 960 | 1150 1285 1416 | |
| | Dimensions(mm)H*W*L | ^^^^^^^^^^^V 1650x1100x800 | 1730x1 195x870 | 1880x1565x925 | |
| | OPTION | S | | |
| | Input Transformer | Input Isolation Transformer | |
| | Input THDI | %10 (12 Pulse or 18 Pulse Rectifier, According to UPS Power) | |
| | %5 (18 Pulse Rectifier, + Filter), Upto 100 kVA | |
| | Input Power Factor | 0.95-0.98 (Upto 100 KVAWith 18 Pulse Rectifier) | |
| | Parallel Operation | N+1 (Upto 4 Pcs) | |
| | | Dimension Could be Different at18 Pulse UP | |
| | | | | | |