200 serie - AC/ DC Electronics - #2

/ 2


catalogue search
P. 01
P. 02
Pages:


See other catalogues for AC/ DC Electronics

Text version of the page
AC/DC UPS
MODEL
206
207
210
215
220
230
Power
6 kVA
7,5 kVA
10 kVA
15 kVA
20 kVA
30 kVA
INPUT
Input Voltage
220/380Vac3Phase + N+/-%15
By-Pass Voltage
220 Vac+/-% 10
Current
3x12A 3x15A 3x20A 3x30A 3x40A 3x60A
Input Frequency
50 Hz. +/- %5
EMI
EN50091-2 Class A
OUTPUT
Power (kW)
4,2 5,25 7 10,5 14 21
Power Factor
0,7
Voltage
220 Vac
Voltage Tolerance
+/-% 1
Frequency
50 Hz
Frequency Tolerance
(Synchronised to Line): +/- 2% - (Free Operation): +/-%0,2
Efficiency (at % 100 Load)
%86-90
Crest Factor
3:1
OverLoad
(at % 100-%125 Load: 10 minutes.) (at % 125-%150 Load: 1 minute.) (>% 150 Load: By-Pass)
Shortcircuit Protection
Electronical Short Circuit Protection
THD
<%3
Communication
DryContactand RS232 Communication
Software
T-Mon Standart SNMP - ModBus (Optional)
BATTERY
Quantity
20
30
Charge Voltage
270VDC
405VDC
End of Discharge Voltage
200VDC
300VDC
Battery Type
DryType Maintenance Free
Battery Cabinet
Internal
Operation Temperature
25°C
Battery Protection
Automatic Circuit Breaker
Battery Test
Optional
*
Standart
Operation Temperature
0C-40C
Noise Level
< 42 dBA
<42dBA
< 45 dBA
<45dBA
<45dBA
<45dBA
Protection Class
^^^^^^^^^^^^^^^^^^^^V IP20
Operation Height
< 1000 m.FromSea Level
Humidity (Not Condensed)
< 90 % Max.
Weight (Without Battery)
50
55
55
65
91
112
Dimensions (mm) H-W-L
540x265x560
540x265x560
710x265x740
710x265x740
710x265x740
710x265x740
OPTIONS
Input Transformer
Input Isolation Transformer
PFC
^ Input PFC{>0,97)
Maintenance By-Pass
Isolation of UPS During Maintenance
Parallel Operation
N+1 {Upto 4 Pes)
PerpaTicaret Merkezi ABIok Kat: 8 No: 851 Okmeydani 34384, istanbuI Tel :+90 212 320 20 07 Pbx Faks :+90 212 320 20 09 info@acdc.com.tr www.acdc.com.tr

pageCatalog pdf di En 2012-05-21-23