100 serie - AC/ DC Electronics - #2

/ 2


catalogue search
P. 01
P. 02
Pages:


See other catalogues for AC/ DC Electronics

Text version of the page
AC/DC UPS
MODEL
102
103
105
107
110
115
Power
2kVA 3kVA 5kVA 7 kVA 10 kVA 15 kVA
INPUT
InputVoltage
220 Vac +/-% 15
By-Pass Voltage
220 Vac +/-% 10
Current
13A 20A 35A 45A 60A 85A
Input Frequency
50 Hz. +/- %5
EMI
EN50091-2 Class A
OUTPUT
Power(kW)
1,4 2,1 3,5
4,55
7 10,5
Power Factor
0,7
0,65
0,7
Voltage
220 Vac
Voltage Tolerance
+/-% 1
Frequency
50 Hz
Frequency Tolerance
(Synchronised to Line): +/- 2% - (Free Operation): +/-%0,2
Efficiency (at % lOOLoad)
%85-87 %85-87 %85-87 %85-87 %86-90 %86-90
Crest Factor
3:1
OverLoad
(at % 100-%125 Load: 10 dk.) (at % 125-%150 Load: 1 dk.) (>% 150 Load: By-Pass)
Shortcircuit Protection
Electronic Short Circuit Protection
THD
<%3
Communication
DryContactand RS232 Communication
Software
T-Mon Standart SNMP - ModBus (Optional)
BATTERY
Quantity
14
14
16
18
20
20
ChargeVoltage
189 VDC
189VDC
216V
243 V
270 V
270 V
EndofDischargeVoltage
140VDC
140VDC
160 V
180V
200 V
200 V
BatteryType
DryType Maintenance Free
BatteryCabinet
Internal | External
Operation Temperature
25°C
Battery Protection
Automatic Circuit Breaker
BatteryTest
Optional
Operation Temperature
0C-40C
Noise Level
<42dBA <42dBA <45dBA <45dBA <45dBA <45dBA
Protection Class
^^^^^^^^^^^^^^^^^^^^V IP20
Operation Height
< 1000 m.FromSea Level
Humidity(Not Condensed)
< 90 % Max.
Weight (Without Battery)
50
55
60
75
91
112
Dimensions(mm) H-W-L
540x265x560
540x265x560
585x265x600
635x265x665
710x265x740
710x265x740
OPTIONS
InputTransformer
Input Isolation Transformer
PFC
^ Input PFC(>0,98)
Maintenance By-Pass
Isolation of UPS During Maintenance
Parallel Operation
N+1 (Upto 4 Pes)
PerpaTicaret Merkezi ABIok Kat: 8 No: 851 Okmeydani 34384, istanbuI Tel :+90 212 320 20 07 Pbx Faks :+90 212 320 20 09 info@acdc.com.tr www.acdc.com.tr

pageCatalog pdf di En 2012-05-21-23