Technical Data REX 521
Protection functions
Condition monitoring and self-supervision
The REX 521 relay incorporates a large number of supervision functions for con­stant monitoring ofthe relay's operational preparedness. On the relay input side both voltage and current measuring circuits are continuously supervised. On the relay out­put side the trip circuits, including the CB trip coils, are constantly supervised for loss of control voltage or trip circuit dis­continuity. Further, the condition of the circuit breaker can be monitored for me­chanical wear on the main contact. The auxiliary supply of the relay and the internal relay voltages are supervised by the relay's integrated self-supervision system, which also incorporates watchdog functions su­pervising the operation of the relay.
A step into intelligent substation automation
The REX 521 relays are fully integrated into ABB's distribution automation and network management systems. The support for all major communication protocols and stan­dards, including the new IEC 60850 stan­dard, makes the relay a perfect fit for your network control and management system. In addition to protection, REX offers exten­sive measurements including phase cur­rents, neutral current, line voltages, residual voltage, system frequency, power factor, active and reactive power, total harmonic distortion (THD) and power quality. Any doubtful event in the power system can be recorded by the built-in high-sampling-frequency disturbance recorder for subse­quent disturbance or fault analysis.
ANSI number
• 3I>, 31», 3I»> 50/51
3-phase non-directional overcurrent protection, 3 stages
• 3I>-, 3I>>- 67
3-phase directional overcurrent protection, 2 stages •3I< 37
3-phase undercurrent protection
•Io>, Io>>, Io>>> 50N/51N
Non-directional earth-fault protection, 3 stages
•I0>-, I0>>-, I0>>>- 67N
Directional earth-fault protection, 3 stages
•U0>, U0», U0»> 59N
Residual overvoltage protection, 3 stages
• 3U>, 3U>> 59 3-phase overvoltage protection, 2 stages
• 3U<, 3U<< 27 3-phase undervoltage protection, 2 stages •3I2f> 68 3-phase transformer inrush and motor start-up current
detector
• AI> 46
Phase discontinuity protection
•35 49F
3-phase thermal overload protection
•0-1 79
Auto-reclosefunction (5 shots)
• f</f>, df/dt 81U7810 Underfrequency/overfrequency protection
• SYNC 25 Synchro-check/voltage-checkfunction
•3J 49M/49G/49T
Three-phase thermal overload protection for devices •Is2t n< 48/14/66
Three-phase motor start-up supervision •3I ^,3I^ 46R
Phase reversal protection
•I2>, I2>> 46
Negative phase sequence protection with two stages •U1<, U2>, U1> 27/47/59
Phase sequence voltage protection
• FUSEF 60
Fuse failure protection
• CBFP 62BF
Circuit-breaker failure protection Included into every protection function
Control Functions:
I<->0 CB1 Circuit breaker control & indication
with adjustable closing delay I<->0IND1-3 Objectlndication I<->0 POS Logic control position selection ALARM1-8 AlarmLEDs1-8
Monitoring and supervision:
CB wear Circuit-breaker condition monitoring
TCS1 Trip-circuitsupervision
MCS 3I Energizing current circuit supervision
MCS 3U Energizing current circuit supervision
TIME1 Operation time counter
Measurements: Primary and unitvalues
3I 3-phase current measurement
I0 Neutral current measurement
U0 Residual voltage measurement
3U 3-phasevoltagemeasurement
System frequency measurement
E,P,Q,pf 3-phase power and energy (ncl. cos (p) DREC Transient disturbance recorder
AI1 Analog measuring function
PowerQuality:
THD Current and voltage distortion
measurements(1-13th harmonics) PQ3Inf Current waveform distortion
measurement
PQ3Unf Voltagewaveformdistortion
measurement
GENERAL:
• Non-volatile memory
• Ninedigital inputs
• Four power outputs
• Two signalling outputs
• User-configurable Alarm LEDs
• Internal relay fault output
CCoEmCm0n7C0a-5o^CNon.^eSC^A:^ odbus. RTU/ASCII, DNP 3.0, Profibus-DPVI, IEC 61850 (with interface adapter) <
• Connectivity package ;
Dimensions: {
Width148.8mm(1/3ofa19"rack), i
Height frame 265.9 mm (6U) =
Box 249.8 mm i
Depth 235 mm i