Motor Protection and Control REM615 Product Guide
56Pages

{{requestButtons}}

Catalog excerpts

Motor Protection and Control REM615 Product Guide - 2

Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumesno responsibility for any errors that may appear in this document. Copyright 2009 ABB Oy.All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders. >

Open the catalog to page 2
Motor Protection and Control REM615 Product Guide - 3

REM615 is a dedicated motor protection andcontrol IED (intelligent electronic device) designed for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry. REM615 is a member ofABBs Relion > Ү and DNP3. > product family and part of its615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable design.Re-engineered from the ground up, the 615series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between...

Open the catalog to page 3
Motor Protection and Control REM615 Product Guide - 4

Table 2. Supported functions Functionality C Protection > 1) Thermal overload protection for motors Ⴠ Motor start-up supervision Ⴠ Negative-sequence overcurrent protection for motors, instance 1 Ⴠ Negative-sequence overcurrent protection for motors, instance 2 Ⴠ Directional earth-fault protection, low stage, instance 1 Ⴠ Non-directional earth-fault protection, using calculated I > Ⴠ Motor load jam protection Ⴠ Three-phase non-directional overcurrent protection, low stage, instance 1 Ⴠ Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Ⴠ Loss of load...

Open the catalog to page 4
Motor Protection and Control REM615 Product Guide - 5

Table 2. Supported functions, continued Functionality C Trip circuit supervision, instance 1 Ⴠ Trip circuit supervision, instance 2 Ⴠ Current circuit supervision Ⴠ Fuse failure supervision Ⴠ Motor runtime counter Ⴠ Measurement Disturbance recorder Ⴠ Three-phase current measurement Ⴠ Sequence current measurement Ⴠ Residual current measurement Ⴠ Three-phase voltage measurement Ⴠ Residual voltage measurement Ⴠ Sequence voltage measurement Ⴠ Three-phase power and energy measurement ჀჀ = included, o = optional at the time of order > 1)Note that all directional protection functions can also be...

Open the catalog to page 5
Motor Protection and Control REM615 Product Guide - 7

REM615 constitutes main protection forasynchronous motors and the associated drives. Typically, the motor IED is used with circuit-breaker or contactor controlled HV motors, and contactor controlled medium sized and large LV motors in a variety of drives, such as pumps and conveyors, crushers and choppers, mixers and agitators, fans and aerators. The motor IED is thoroughly adapted for earth-fault protection. Using cable current transformers sensitive and reliable earth-fault protection can be achieved. The earth-fault protection can also utilize phase current transformers in Holmgreen...

Open the catalog to page 7
Motor Protection and Control REM615 Product Guide - 9

Table 3. Supported ABB solutions ABBs 615 series protection and control IEDstogether with the COM600 Station Automation device constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systems. To facilitate and streamline the system engineering ABBҒs IEDs are supplied with Connectivity Packages containing a compilation of software and IED-specific information including single-line diagram templates, a full IED data model including event and parameter lists. By utilizing the Connectivity Packages the IEDs can be readily configured via the PCM600...

Open the catalog to page 9
Motor Protection and Control REM615 Product Guide - 11

By default, the binary channels are set torecord external or internal IED signals, for example the start or trip signals of the IED stages, or external blocking or control signals. Binary IED signals such as a protection start or trip signal, or an external IED control signal over a binary input can be set to trigger the recording. The recorded information is stored in a non-volatile memory and can be uploaded for subsequent fault analysis. The condition monitoring functions of theIED constantly monitors the performance and the condition of the circuit breaker. The monitoring comprises the...

Open the catalog to page 11
Motor Protection and Control REM615 Product Guide - 12

The IED includes fuse failure supervisionfunctionality. The fuse failure supervision detects failures between the voltage measurement circuit and the IED. The failures are detected by the negative- sequence based algorithm or by the delta voltage and delta current algorithm. Upon the detection of a failure the fuse failure supervision function activates an alarm and blocks voltage-dependent protection functions from unintended operation. The IED is equipped with three phase-current inputs, one residual-current input, three phase- voltage inputs and one residual voltage input. The...

Open the catalog to page 12
Motor Protection and Control REM615 Product Guide - 13

Table 4. Input/output overview Standardconfiguration Analog inputs Binary inputs/outputs CT VT BI BO C 4 5 > 1) 16 10 > 1)One of the five inputs is reserved for future applications The IED supports a range of communication protocols including IEC 61850, IEC60870-5-103, Modbus > and DNP3.Operational information and controls are available through these protocols.The IEC 61850 communicationimplementation supports all monitoring and control functions. Additionally, parameter setting and disturbance file records can be accessed using the IEC 61850 protocol. Disturbance files are available to any...

Open the catalog to page 13
Motor Protection and Control REM615 Product Guide - 14

ModbusՕDNP3IEC 60870-5-103 Table 5. Supported station communication interfaces and protocols Interfaces/Protocols Ethernet Serial 100BASE-TXRJ-45 100BASE-FX LC RS-232/RS-485 Fibre-optic ST IEC 61850 աÀ Ⴠ - - MODBUS RTU/ ASCII - - Ⴠ Ⴠ MODBUS TCP/ IP Ⴠ Ⴠ - - DNP3 (serial) - - Ⴠ Ⴠ DNP3 TCP/IP Ⴠ Ⴠ - - IEC 60870-5-103 - - Ⴠ ჀჀ = Supported >

Open the catalog to page 14
Motor Protection and Control REM615 Product Guide - 15

Table 6. Dimensions Description Value Width frame 179.8 mm case 164 mm Height frame 177 mm (4U) case 160 mm Depth 194 mm (153 + 41 mm) Weight IED 3.5 kg spare unit 1.8 kg Table 7. Power supply Description Type 1 Type 2 U > aux nominal 100, 110, 120, 220, 240 V AC,50 and 60 Hz 24, 30, 48, 60 V DC 48, 60, 110, 125, 220, 250 V DC U > aux variation 38...110% of U > n (38...264 V AC) 50...120% of U > n (12...72 V DC) 80...120% of U > n (38.4...300 VDC) Start-up threshold 19.2 V DC (24 V DC * 80%) Burden of auxiliaryvoltage supply under quiescent (P 250 V DC ~ 9.0 W (nominal)/~13.7 W (max) 240 V...