≤ 50 mA constantlyError limit 0.5 %

Technical DataREG-DA

≤ 1.5 VElectrical isolation Optocoupler Common mode rejection > 80 db Series mode rejection > 60 db / decade ex 10 Hz Overload capacity

Voltage Regulator REG-DA - 15254 Technical characteristics,

Analogue inputs (AE) Regulations and standards

Number Refer to the order details Input range X1…X2 -20 mA…0…20 mA X1 and X2 programmable Control limit ± 1.2 X2 Voltage drop IEC 1010/ EN61010 (VDE 0411)CAN / CSA - C 22.2 No. 1010.1 - 92 VDE 0110 IEC 255 - 4 DIN 43807 EN 61326 - 1 / A1 IEC 688 - 1 IEC 529 EN 50178 / VDE 0160 / 11.94 (currently draft) VDE0106 part 100 The regulator is equipped with an analogue input as stan-dard.The inputs can be continuously short-circuited or operated open. All inputs are galvanically isolated from all other cir- cuits.

UL Certifi cate Number 050505 - E242284

Temperature input PT 100

Number Only one PT 100 input possible Connection 3-conductor circuit Current through sensor

Resistance input for tap-changepotentiometer:

Ω when total resistance is 20 k Ω ) into tap-change positions.Pins 23 to 26 intended for connection to tap-change poten-tiometers. A current is connected via pins 23 and 26 and a resistance chain. The voltage drop that occurs per tap-change position can be measured via pins 24 and 25 (4-conductor circuit) or via pins 23 and 25 (3-conductor circuit). The standard version is a 3-conductor circuit. If a 4-conductor measurement circuit is required, it can be achieved at any time by changing the switching settings of DIP switch S and the connection.The resistance measurement circuitry consists of a program-mable current source to feed the measurement resistance and a voltage-measurement device to measure the voltage at the resistance. The measurement result is output with a resolution of 12 bits and a refresh rate of approx. 10 Hz (0.1 s).The measurement device has a broken-wire detection sys-tem. The parameters can be entered into an application menu using the keyboard (see operating manual). REG-DA voltage regulators that are equipped with characteri- stics D2 or D3 have only 8 binary inputs as standard, but also have a resistance input that can transform the resistance of the tap-change potentiometer (200

AC voltage input (U

E

)

Measurement voltage U
E 60 ... 140 V (if three-phase voltage is connected) 35 ... 80V (if a phase voltage is connected) The nominal value can be selected using software Curve shape Sinusoidal Frequency range 16....50....60....65 HzInternal consumption ≤ U
2 / 100 k Ω Overload capacity 300 VAC constantly

AC current input (I

(software-selectable)Curve shape SinusoidalFrequency range 16....50....60....65 HzControl range 0 ... In ... 2.1 In Internal consumption
E

)

Measurement current In 1 A / 5 A ≤ 0.5 VAOverload capacity 10 A constantly 100 In for 1 sec 30 In for 10 sec
A. Eberle GmbH & Co. KG4